The quality of survival, technology and development
Quality for survival, technology for development
YB-12/0.4 type High-Voltage/Low-Voltage Prefabricated Substation
YB-12/0.4 type High-Voltage/Low-Voltage Prefabricated Substation
YB-£12/0.4 type High-Voltage/Low-Voltage Prefabricated Substation

Description:

YB-£12/0.4 type High-Voltage/Low-Voltage Prefabricated Substation can realize ring main type and terminal type power supply mode. It’s applicable to urban public power distribution, street lamp electricity, industrial and mining enterprises, etc.. In addition, it meets the Standards GB/T17467 and IEC601330.

Structure features:

u Small size, light weight, beautiful appearance and environmental coordination.

u Composed of a high pressure chamber, a transformer chamber and a low pressure chamber.

u Terminal, ring or dual power supply.

u Single or dual transformer power supply solution.

u Oil-immersed power and Dry power transformer.

u Sufficient natural vents and insulation measures (forced cooling if need).

u Multiple materials or a combination of both help long-term use outdoor.

u Small size when using SF6 load switch cabinet, and suitable for community construction, street lighting engineering renovation.

u Reliable detection of short-circuit and single-phase ground faults because of RTU in the high-voltage ring main cabinet.

u Complete and reliable Five-protection system. Easy to operate and maintain.

Using environment:

u Temperature: Min -45℃~Max+40℃;

u Relative humidity: Daily average ≦95%; Monthly average≦90%;

u Altitude: ≦1000m;

u Shock level: Horizontal acceleration 0.4m/s2,Vertical acceleration 0.15m/s2;

u Installation location: The place with no severe impact, serious pollution and chemical corrosion, no conductive dust and explosion risk.

When the conditions of use exceed the above range, the user shall negotiate with us to determine the allowable range or take corresponding supplementary technical measures.

Item

Unit

Value

High-Voltage unit

Rated frequency

HZ

50

Rated voltage

KV

10

Maximum working voltage

KV

11.5

Rated current

A

400630

Take-over current

A

870

Power frequency withstand voltage (Phase to phase, Phase to ground/Isolation fracture)

KV

42/48

Lightning impulse withstand voltage(Phase to phase, Phase to ground/Isolation fracture)

KV

75/85

Rated short-circuit breaking currentCurrent limiting fuse

KA

31.5

Transformer unit

Rated voltage

KV

610

Rated Capacity

KV/A

10-1250

Tap range

%

±2*2.5%、±5%

Connection group

 

Yyn0Dyn11

Impedance voltage

%

44.568

Low-Voltage unit

Rated voltage

V

220380690800

Main circuit rated current

A

50-4000

Branch current

A

5-800

Shell

IP gradeConventional product

 

High-Voltage Room IP33; Transformer Room IP23; Low-Voltage Room IP33

Noise level

dB

50

Technical Parameters:


Product details